A244 DRIVEFLEX® Control Pair(s)

LUTZE Driveflex A244
Application
  • Easily add control pairs to any VFD circuit
  • Twisted shielded pair cable for VFD & motor applications to transmit control signals from drives to motors
  • Separating control from power allows full ampacity rating of the power cable
  • Cable design for harsh industrial environments and operating conditions with high noise levels
  • Thermoset XLPE insulation offering superior overload and short-circuit temperature
  • Compliant with NFPA 79 requirements
  • TC-ER for use with cable trays without conduit and alongside power tray cables
  • WTTC – wind turbine tray cable rating for use in wind power generation
  • Dry, damp or wet conditions
Characteristics
  • Flexible XLPE conductor design
  • High insulation resistance
  • Low capacitance cable
  • Effective dual layer shield for EMC compliance
  • Oil resistant jacket designed for easy stripping
  • Non-wicking fillers
  • Ecolab certified resistance to common cleaning agents and chemicals used in food and beverage washdown procedures
  • Crush impact resistant
  • Gas/vapor-tight sheath per UL 1277 
  • Sunlight resistant
  • Flame retardant
  • Direct burial
  • Talc and silicone free
Part number Description No. of conductors incl. ground OD - Ø ca. mm OD - Ø ca. inches Weight Lbs/Mft Copper Lbs/Mft
A2441802 AWG 18 (16/30)
1 TSP AWG 18 (16/30)
1 pair
8.7 0.344 77 29
A2441602 AWG 16 (26/30)
1 TSP AWG 16 (26/30)
1 pair
9.4 0.370 88 36
A2441402 AWG 14 (41/30)
1 TSP AWG 14 (41/30)
1 pair
10.2 0.400 108 51
A2441804 AWG 18 (16/30)
2 TSP AWG 18 (16/30)
2 pairs
14.0 0.550 164 58
A2441604 AWG 16 (26/30)
2 TSP AWG 16 (26/30)
2 pairs
15.5 0.610 189 73
A2441404 AWG 14 (41/30)
2 TSP AWG 14 (41/30)
2 pairs
16.6 0.655 237 102
Voltage:

600V 90C TC-ER


1000V 90C Flexible VFD Servo Cable


1000V 90C WTTC

Temperature: -40°C - +90°C static
Bending radius: 6 x cable OD
Conductor marking: Black with white number print
Oil resistance: Oil Res II
Approvals:

UL Type Flexible Motor Supply Cable,


Flexible VFD Servo Cable,


UL Type TC-ER, WTTC


Meets NEC 336, 392 Class I & II Div. 2 and Class I Zone 2 per NEC 501, 502, 505


c(UL) TC, CIC FT4


UL 1277


RoHS, REACH, TSCA

Construction:

AWG conductor


Class K flexible fine wire stranded tinned copper conductors for improved electrical characteristics and reduced oxidation


Thermoset XLPE insulation type XHHW-2, Wet/Dry


Each pair shielded with foil tape, drain wire, tinned copper


braid (≥ 80% optical coverage), then wrapped in clear foil


Oil resistant PVC jacket


Black jacket similar to RAL 9005



Specifications subject to change without prior notice